Function 66 (Measure)
Master >>> Slave
Byte
number
Value / variable Range Definition
1 ADDEV
0..31 Slave address in the rs485 network
2 66 (42h)
0..255 Function number
3 Wym_kan_1
0..3
0- °C
1- %
2- bar
3- „clock”
4 Wym_kan_2 0..3 As before
5 Wym_kan_3 0..3 As before
6 Wym_kan_4
0..3 As before
7 Wym_kan_5
0..3 As before
8 Wym_kan_6
0..3 As before
9 Wym_kan_7
0..3 As before
10 Wym_kan_8
0..3 As before
11 CRC_h
0..255
12 CRC_l 0..255
CRC-16 control total